GATE Electrical Engineering (EE) 2017 Shift 2 Solved Paper
© examsiri.com
Question : 62 of 65
Marks:
+1,
-0
A 3-phase, 50 Hz generator supplies power of 3 MW at 17.32 kV to a balanced 3-phase inductive load through an overhead line. The per phase line resistance and reactance are 0.25 Ω and 3.925 Ω respectively. If the voltage at the generator terminal is 17.87 kV, the power factor of the load is ________.
- Your Answer:
Go to Question: