GATE Electrical Engineering (EE) 2014 Shift 2 Solved Paper
© examsiri.com
Question : 53 of 65
Marks:
+1,
-0
A three phase, 100 MVA, 25kV generator has solidly grounded neutral. The positive, negative, and the zero sequence reactances of the generator are 0.2 pu, 0.2 pu, and 0.05 pu, respectively, at the machine base quantities. If a bolted single phase to ground fault occurs at the terminal of the unloaded generator, the fault current in amperes immediately after the fault is________.
- Your Answer:
Go to Question: