GATE Electrical Engineering (EE) 2014 Shift 1 Solved Paper

© examsiri.com
Question : 53 of 65
 
Marks: +1, -0
The overcurrent relays for the line protection and loads connected at the buses are shown in the figure.

The relays are IDMT in nature having the characteristic
top=0.14× Time Multiplier Setting ( Plug Setting Multiplier )0.02−1
The maximum and minimum fault currents at bus B are 2000 A and 500 A respectively. Assuming the time multiplier setting and plug setting for relay RB to be 0.1 and 5A respectively, the operating time of RB (in seconds) is_______