GATE Electrical Engineering (EE) 2011 Solved Paper
© examsiri.com
Question : 63 of 65
Marks:
+1,
-0
Two generator units G1 and G2 are connected by 15kV line with a bus at the mid-point as shown below
G1 = 250 MVA, 15 kV, positive sequence reactance XG1 = 25% on its own base
G2 = 100 MVA, 15 kV, positive sequence reactance XG2 = 10% on its own base L1 and L2 = 10 km, positive sequence reactance XL = 0.225 Ω/km
In the above system, the three – phase fault MVA at the bus 3 is
G1 = 250 MVA, 15 kV, positive sequence reactance XG1 = 25% on its own base
G2 = 100 MVA, 15 kV, positive sequence reactance XG2 = 10% on its own base L1 and L2 = 10 km, positive sequence reactance XL = 0.225 Ω/km
In the above system, the three – phase fault MVA at the bus 3 is